Grinding, Sulfur Capping or Unbonded Pads: Preparing the Ends of Concrete Cylinders and Cores

A concrete cylinder is cast to measure one number, and most of the work that decides whether that number is right happens at its two ends. The compression machine loads the specimen through its end faces. If those faces are not flat, or not square to the axis, the platens touch a high spot or an edge first, the load runs through part of the section instead of all of it, and the cylinder breaks early. The report then shows a low strength for a concrete that was never weak.

There are three accepted ways to give a cylinder or a core usable ends: grind them flat, cap them with a bonded material such as sulfur mortar, or seat them in unbonded elastomer pads held in steel retainers. ASTM C39 lists all three as routes to a specimen it will accept. They are not interchangeable, though, and the differences grow with the strength of the concrete. This guide sets out what each method requires, where each one runs out, and how cores add their own complications.

What the Ends Have to Achieve

The requirement behind every method is the same: two load-bearing faces that are plane and perpendicular to the specimen’s axis. Free summaries of C39 from FHWA and NRMCA give the figures most laboratories work to: ends plane within 0.050 mm (0.002 in), and no departure from perpendicularity of more than 0.5 degree, which is about 1 mm across a 100 mm diameter. A specimen whose ends miss those limits is sawed or ground until it meets them, or capped under ASTM C617 or, where permitted, ASTM C1231.

Half a degree sounds generous until it is drawn. On a 150 mm cylinder it is a wedge of about 1.3 mm from one side of the face to the other, more than twenty times the planeness limit. A platen meeting that face touches one edge first and has to crush it before the rest of the section carries load. The European standard expresses the same idea in proportion to size: EN 12390-1 sets the flatness of a load-bearing surface at 0.0006 times the diameter, about 0.09 mm on a 150 mm cylinder.

Why the ends decide the result
Half a Degree Across the Face
WHAT HALF A DEGREE LOOKS LIKE: SIDE VIEW, END ERROR EXAGGERATED 20 TIMESfirst contact1.31 mm gapØ150 mm cylinder: 0.5° = 1.31 mm across the facefirst contact0.87 mm gapØ100 mm cylinder: 0.5° = 0.87 mm across the faceTHE LIMITS LABORATORIES WORK TOPlaneness0.050 mm (0.002 in)C39, as summarised by FHWA and NRMCAPerpendicularity0.5 degreeabout 1 mm across 100 mmEN 12390-1 flatness0.0006 x diameter0.09 mm on a 150 mm cylinderThe wedge is many times the planeness limit.
An end that is half a degree off square leaves a wedge of 1.31 mm across a 150 mm cylinder and 0.87 mm across a 100 mm one, drawn here with the vertical scale exaggerated twenty times. The platen meets the high edge first, many times beyond the 0.050 mm planeness limit.
Scroll the diagram sideways to see all of it.

How much a flaw costs depends on the strength of the concrete, and the effect has been known for a century. In the tests reviewed by NIST, an end convexity or concavity of 0.08 mm made no difference on concretes of 15 to 24 MPa, but deviations of 0.25 mm or more reduced strength significantly, and the loss grew as the concrete got stronger. The stronger and stiffer the concrete, the less a small error in the end is forgiven.

Laboratories catch most bad ends before the specimen reaches the machine. The Washington State DOT checklist for cylinder compression testing under AASHTO T 22 has the technician check the ends of each specimen for plane and for perpendicularity, and send any that fail to the saw, the grinder or the capping station. State technician training adds a quicker screen: a carpenter’s square laid across the end, and if the highest and lowest points differ by more than about 3 mm (1/8 in), the cylinder is cut or ground before any cap goes on. The diameter is measured twice at mid-height as well, and a specimen whose two readings differ by more than 2 percent is not tested.


Three Ways to Make the Ends Right

Each method solves the same geometric problem in a different way. Grinding removes material until the face is flat and square. A bonded cap adds a thin layer of stiff material that fills the irregularities and presents a new flat face. An unbonded pad adds a soft layer that flows into the irregularities under the first load, held in a steel ring so it cannot spread sideways.

Grinding

NG-CoreGrind 1000 semi-automatic core grinding machine with water spray hose
NG-CoreGrind 1000. Adapters from 25 mm cores to 150 by 300 mm cylinders, with water spray.

Grinding produces an end that is concrete all the way to the platen, with nothing between them to deform, set, age or be qualified. That is its main advantage and the reason the European core standard, EN 12504-1, notes that end preparation by grinding is recommended as the most precise method. AASHTO went a step further in 2024 with R 119M/R 119, a standard practice devoted to grinding the ends of cylindrical concrete specimens, written with ultra-high-performance concrete in mind, and the 2026 edition of C39 now lists it among the practices that prepare specimens for testing. A ground cylinder is ready to test as soon as it is ground, and the result does not depend on the age or strength of a capping compound.

Grinding is wet work. A diamond wheel cuts the face under a water spray, which also keeps the dust down, and the machine has to hold the specimen square while the wheel passes across it. That is what separates a grinder built for this job from a general surface grinder: the fixture decides the perpendicularity, and the wheel decides the flatness.

Bonded Caps: Sulfur Mortar, Gypsum and Cement Paste

ASTM C617 covers bonded caps of neat cement paste on freshly molded cylinders and of high-strength gypsum paste or sulfur mortar on hardened cylinders and drilled cores. Bonded caps remain common: the FHWA laboratory manual estimates that about a quarter of US laboratories use them as their primary end treatment. They work well when they are thin, strong and bonded across the whole face. Free state DOT training material on C617 describes the limits: for cylinders from 500 to 7000 psi, a cap no thicker than 8 mm anywhere and 6 mm on average, made of material with a strength of at least 5000 psi or the cylinder’s strength, whichever is greater; above 7000 psi, no thicker than 5 mm and 3 mm on average, and at least as strong as the concrete or qualified against ground or paste-capped companions.

Sulfur caps also need time. The same training material calls for at least 2 hours of hardening before testing below 5000 psi and 16 hours at 5000 psi and above unless qualification shows less. Pure sulfur is a poor capping material on its own: the NIST review records a compressive strength of about 16 MPa and a stiffness around a tenth of concrete’s, which is why capping compounds carry sand or fly ash. And sulfur capping carries a hazard grinding does not. The melting pot must sit under a hood or next to an exhaust fan, because sulfur mortar contaminated with oil or other organic material can produce hydrogen sulfide, which is lethal in high concentrations and cannot be trusted to give itself away by smell.

Most cap problems are found by routine checks rather than by a low result. The FHWA manual names the usual errors: voids where moisture under the cap turned to vapor, and misuse of the alignment device, which loads the specimen off-center. Against them, the training material sets clear controls: the alignment device holds the cap within 0.5 degree of perpendicular and no more than 1.6 mm (1/16 in) off-center, and at least three capped specimens per run, at its start, middle and end, are checked with a straightedge and feeler gauge across three diameters. The capping material is tested on 50 mm (2 in) cubes for each new lot and at least every three months, sulfur mortar is reused no more than five times and not at all for concrete above 5000 psi, and above 7000 psi a material weaker than the concrete is qualified on 30 cylinders: 15 capped with it and 15 ground or capped with neat cement paste, with the first set averaging at least 98 percent of the second.

Unbonded Caps: Neoprene Pads in Steel Retainers

ASTM C1231 allows unbonded caps on molded cylinders and on drilled cores in place of C617 caps. An elastomer pad, typically about 13 mm thick, sits in a steel retainer whose inside diameter is slightly larger than the specimen. On the first loading the pad deforms to follow the end, and the retainer stops it spreading. There is nothing to melt, mix or wait for, which is why pads are popular in high-volume laboratories.

Their range is fixed by the standard. Unbonded caps are not used for acceptance testing of concrete below 10 MPa or above 80 MPa. Within that range, neoprene pads of a stated hardness can be reused a set number of times without qualification up to a strength limit, and above it, qualification is required. The DOT training material gives the usual table: 50 durometer pads for 1500 to 6000 psi, 60 for 2500 to 7000 psi, 70 for 4000 to 7000 psi, all without qualification and up to 100 uses, and 70 durometer pads from 7000 to 12,000 psi only with qualification and up to 50 uses. ASTM also warns that specimens tested with unbonded caps rupture more violently than comparable specimens with bonded caps, so containment around the platens matters more.

Pads cope with rougher ends than bonded caps do. NRMCA’s guidance puts the limit for bonded caps at surface defects under about 3 mm and for unbonded systems at about 5 mm, and anything worse is sawed or ground before the pad goes on.

Pads trade the capping station for bookkeeping. The pad is 13 mm (1/2 in) thick within 1.6 mm, its retainer has an inside diameter of 102 to 107 percent of the cylinder’s, and a pad outside those limits or past its reuse count is replaced. Laboratories keep a record of the date each pad went into service, its durometer and its number of uses. Qualification pairs cylinders at both the highest and the lowest strengths expected, ten pairs at each level, one of each pair with pads and the other ground or capped, and the pad average must reach at least 98 percent of its companions. The specimen’s alignment is checked after load is applied but before 10 percent of the expected maximum, since FHWA notes that with unbonded caps a corner fracture can occur before the cylinder reaches its ultimate capacity.


When the Method Changes the Number

The clearest data on grinding against capping comes from a NIST study sponsored by FHWA, which tested 100 by 200 mm and 150 by 300 mm cylinders at nominal strengths of 45 and 90 MPa, with ends either capped with sulfur mortar or ground. On average the ground cylinders were 2.1 percent stronger. At 45 MPa the end preparation made no difference. At 90 MPa grinding gave up to 6 percent higher strength in some combinations, with caps under 4 mm thick, and the authors expected larger differences with thicker caps. Their recommendation for concrete above 50 MPa was a performance requirement that a capping method should not average lower than grinding.

Another study at 50, 75 and 120 MPa found that sulfur caps applied 2 hours before the test read 2 to 7 percent below ground ends, while caps applied 7 days before matched them, except for thick caps on the 120 MPa concrete. The mechanism is the one the older literature describes: a cap that is softer than the concrete squeezes outward under load, adds lateral tension at the end of the specimen and lowers the reading. A thin, stiff, fully hardened cap behaves almost like concrete. A thick or young one does not.

Where each method runs out
The Window Narrows as Strength Rises
WHICH END PREPARATION IS RECOGNISED, BY CONCRETE STRENGTH020406080100120140compressive strength, MPaGround endsno capping material between concrete and platenBonded caps, C617up to 8 mm3 mm average, qualifiedthinner and qualified as strength risesUnbonded pads, C1231no qualificationqualified, 50 usesnot for acceptance below 10 or above 80Core caps, EN 12504-1caps allowedgrindno sulfur or CAC caps above 50 MPa (2:1)the reference method in the studies; R 119 grinds UHPC
Bonded caps get thinner and need qualification above about 48 MPa (7000 psi). Unbonded pads are not used for acceptance below 10 MPa or above 80 MPa and need qualification above 48 MPa. EN 12504-1 rules out sulfur and calcium aluminate caps on 2:1 cores above 50 MPa. Ground ends carry no capping layer at any strength.
Scroll the diagram sideways to see all of it.

Read together, the standards and these studies give a practical picture. For ordinary strengths, all three methods are recognized and, done correctly, agree closely. As strength rises, the window narrows: caps have to be thinner, stronger, older and qualified, pads need qualification and lose reuses, and above 80 MPa pads are excluded altogether. Grinding is the one method that does not get harder as the concrete gets stronger, which is why it is the reference method in the studies above and the method AASHTO standardized for ultra-high-performance concrete.

Grinding has a limit of its own, and the early UHPC work shows where it lies. In FHWA’s 2006 study of ultra-high-performance concrete, 76 by 152 mm cylinders expected to exceed 83 MPa were ground, while weaker mixes were sulfur-capped, because at those lower strengths the wheel tended to pull fibers out and leave an uneven end. Planeness was checked on a flat steel plate with a dial gauge reading to 0.025 mm, and ends that failed were reground.


Cores Are a Different Specimen

Drilled cores bring every end problem of a molded cylinder plus several of their own. ASTM C42 covers obtaining, preparing and testing them, and its significance section is candid about how many things move the result: the position of the core in the element, the direction it was drilled, the moisture in it at the time of test, and the ratio of its length to its diameter. A core generally tests lower than a properly molded and cured cylinder of the same concrete at the same age, with no single relationship between the two.

Moisture is the reason cores are handled in a fixed sequence. ASTM notes there is no conditioning procedure that reproduces the moisture state of the concrete in the structure; the procedures exist to make results reproducible between laboratories. As the free DOT summaries of the AASHTO practice describe it, the core is wiped and sealed in a plastic bag soon after drilling, trimmed and ground while any water from those steps can still dissipate, and kept sealed for at least five days before testing. Wet grinding after the sealed period would put water back into the ends, so the order matters.

Cores, step by step
From the Drill to the Platen
A CORE BETWEEN THE DRILL AND THE PLATEN (AASHTO T 24 PRACTICE AS DESCRIBED BY STATE DOTS)1Drillcore at least 94 mm forstrength (C42, per FHWA)2Wipe and sealplastic bag once thesurface looks dry3Trim and grindwhile water from wet workcan still leave4Sealedat least 5 days, for evenmoisture5Testwithin 7 days of drillingEN 12504-1 alternative for sulfur capping: core exposed to laboratory air 16 to 24 h, capped, tested within 24 h.No conditioning reproduces the moisture of the structure; the sequence makes results reproducible (C42).
The sequence state DOTs describe for cores tested under the AASHTO practice: sealed soon after drilling, trimmed and ground while water from those steps can still leave, held sealed at least five days and tested within seven days of drilling.
Scroll the diagram sideways to see all of it.

Length matters as much as the ends. A core is normally trimmed to a length of about twice its diameter, and the C39 correction factors apply when the ratio falls to 1.75 or below: 0.98 at 1.75, 0.96 at 1.50, 0.93 at 1.25 and 0.87 at 1.00. Under the FHWA description of C42, a core for strength testing is at least 94 mm in diameter, and if it is capped, the length is measured again with the caps on. EN 12504-1 prefers a length-to-diameter ratio of 2.0 to compare with cylinders or 1.0 to compare with cubes, and it rules out sulfur or calcium aluminate cement caps when the expected strength is above 50 MPa for a 2:1 core or 60 MPa for a 1:1 core. For strong concrete in Europe, the core ends are ground.

Rock core cutter and masonry saw with orange table for cutting concrete and rock cores to length
Core cutter and masonry saw. A V-block clamp keeps the core from rolling while it is cut to length.

A worked example shows how much can ride on these details. Suppose three cores 94 mm in diameter can only be trimmed to 141 mm, an L/D of 1.50, and they break at 31.0, 32.5 and 29.6 MPa. Each reading is multiplied by 0.96, giving 29.76, 31.20 and 28.42 MPa, an average of 29.79 MPa. A note in C42 cites the ACI 318 criterion: concrete represented by cores is considered structurally adequate if the average of three cores is at least 85 percent of the specified strength and no single core is below 75 percent. For a specified 35 MPa, those limits are 29.75 and 26.25 MPa, so these cores pass by 0.04 MPa. Had the weakest core lost 3 percent to a poorly prepared end, the average would have dropped to 29.51 MPa and the verdict would have reversed. The factors have limits too: a 2016 Auburn University report for the Alabama DOT notes that they are valid for concrete of about 14 to 41 MPa (2000 to 6000 psi), with no guidance from there to 10,000 psi.

Cutting the core to length is the first precision step, not a rough one. A saw cut that leaves the end well off square means more grinding afterward and a shorter specimen. Our article on the core cutter and saw for rock, concrete and masonry covers that step, and for rock cores, where the tolerances are much tighter than for concrete, our guide on rock core preparation and end grinding goes through the rock standard in detail.


Choosing an End Preparation for Your Laboratory

The choice usually comes down to four questions. What strengths do you test, and do any exceed 50 MPa? Do you test cores as well as molded cylinders? How many specimens a day go through the compression machine? And who in the laboratory handles molten sulfur today, under what ventilation?

A laboratory testing ordinary structural concrete in volume can run pads or caps well, provided the pads are tracked for reuse and the caps are checked for planeness and age. A laboratory that tests high-strength concrete, cores for structural assessment, or anything that may be disputed later gains the most from grinding: the method that does not narrow with strength, needs no qualification program for a capping material, takes no curing time, and removes the sulfur pot from the building. The cost is a machine and a few minutes per specimen, set against capping material, fume control, pad replacement and the risk of a low result that was really a bad end.

NextGen supplies the preparation side of that decision: grinders that bring both ends of cylinders, cores and cubes into tolerance, and saws that cut cores to length first. The rock mechanics testing equipment range shows the full preparation line, from cutting to grinding.

From the saw to the platen
End Preparation Equipment
Cut to length, then ground flat and square: the two steps that decide whether a compression result reports the concrete or its ends.
NG-CoreGrind 2000 double-faced grinder for concrete and rock cylinders and cubes
Both ends at once
NG-CoreGrind 2000 Double-Faced Grinder
Two grinding heads finish opposite ends of a cylinder or cube in one setup, so the faces come out parallel to each other, with water cooling from the mains or a recirculating tank.
Cylinders Ø50 to Ø150 mm, cubes 50 to 150 mmFlatness error 0.04 mm or less, verticality 0.1 mm or less
View product
NG-CoreGrind 1000 semi-automatic core grinding machine
Grinding instead of capping
NG-CoreGrind 1000 Semi-Automatic Grinder
Grinds the ends of concrete cylinders and cores, rock and stone as the alternative to C617 capping, with a diamond wheel, built-in water spray and a removable drain filter.
Adapters for 100 x 200 and 150 x 300 mm cylindersStated tolerances 0.050 mm flatness, 0.5° perpendicularity
View product
Rock core cutter and masonry saw for cutting concrete cores and specimens to length
Cutting to length
Rock Core Cutter and Masonry Saw
Cuts hardened concrete, rock and stone cores and specimens to length in a V-block clamp with water circulation. The 450 model covers standard concrete cylinders and most core work.
450 mm or 600 mm bladeCutting depth 175 mm or 250 mm
View product
CoreGrind 3000 automatic rock core grinding machine with water tank
Automatic, for rock cores
CoreGrind 3000 Automatic Core Grinder
A fully automatic rock core grinder with recipe-based operation, pneumatic sample locking and recirculating water spray, commonly paired with the CoreTrim 3000 core cutter.
Core diameters 38 to 160 mm (V1 and V2)7-inch touchscreen, Ethernet connection
View product

For a closer look at the semi-automatic machine, our NG-CoreGrind 1000 review goes through its adapters and setup.

Talk to us about end preparation
Tell Us Your Specimens, Your Strengths and Your Volume
Which specimen sizes you test, 100 by 200 mm, 150 by 300 mm, cores or cubes, the range of strengths you see, whether you cap or use pads today, and how many specimens a day reach the compression machine. That is enough for us to recommend the grinder, the adapters and the saw, and to show how the preparation step fits your workflow.
More on this topic

Keep Reading in Rock Specimen Preparation

See the Rock Specimen Preparation range
Cement & Concrete Testing18 Dec 2024How Material Testing Drives Success in Endurance RacingEndurance racing is the ultimate test of human ingenuity and mechanical resilience. Events like the 24 Hours of Le Mans or the Nürburgring 24-hour race push vehicles to their limits, requiring them to maintain peak performance under relentless pressure. Unlike other forms of motorsport, endurance racing isn't just about speed—it's a marathon where durability, reliability, and efficiency take center stage. Every component, from the engine to the tires, faces extreme conditions: high temperatures, continuous vibrations, and prolonged mechanical stress. A single failure can mean the difference between victory and defeat, or worse, put at risk safety. This is where material testing is crucial. By comprehensively evaluating the strength, durability, and...Read the articleCement & Concrete Testing27 Aug 2024Why NextGen is Your Best Choice for Material Testing EquipmentIn the field of material testing, finding a reliable partner that provides advanced equipment, consumables, and comprehensive services such as calibration, maintenance, and technical support is extremely important. With a large number of companies specializing in material testing equipment, the challenge lies in determining which one truly offers the best solutions. Often, the answer to this question becomes clear only after experiencing their products and services firsthand. NextGen Material Testing, stands out as a leading company in this competitive industry. We supply our clients with cutting-edge equipment designed for a broad range of testing applications. We make sure that our customers have all the necessary consumables and support to keep...Read the articleRock Mechanics Testing25 Sep 2026Direct Shear Testing: Shear Box Setups for Soil and RockA direct shear test looks like the simplest measurement in a geotechnical laboratory. A specimen sits in a split box, one half moves, and the force needed to move it is recorded against the normal load pressing down. There is no chamber, no back pressure, no pore pressure transducer to argue about. That simplicity is exactly why the test is so easy to run badly: almost every decision that changes the answer is made before the motor starts. Three of those decisions do most of the damage. How big the box is relative to what is in the specimen, how the normal stress behaves while the specimen changes volume, and whether the plane being sheared is the one the project actually cares about. The Box Size Is a Measurement Decision A shear box forces failure...Read the articleCement & Concrete Testing8 Sep 2026Manual, Digital or Automatic Blaine: What Changes in the ResultEvery Blaine apparatus on the market measures the same thing by the same principle, and any of them will produce a fineness number. The question a cement laboratory is really deciding is a different one: how much of the procedure stays in the operator's hands, and what that costs in agreement between people, between shifts and between sites. That is worth working through carefully, because the automation level is the one specification on a Blaine apparatus that changes the shape of the uncertainty rather than the size of it. If you are still looking for what the method measures and why fineness matters, our article on what an automatic Blaine apparatus is and does covers that ground first. Four Places Where the Operator Enters the Result A Blaine...Read the articleCement & Concrete Testing5 Aug 2026Vicat Testing and What Cement Setting Time Really Tells YouVicat setting time is a standardized cement paste measurement used for specification compliance and quality control. It identifies when a paste prepared under defined conditions reaches the initial and final set criteria of the selected method. It does not directly predict concrete haul time, cold joint formation, finishing time or field workability, because those depend on the complete mixture: water content, admixtures, aggregates and temperature. This guide covers what Vicat setting time measures, how the apparatus produces the number, which test conditions make results drift, and what separates a manual instrument from an automatic one. Setting Time Is Not Early Strength Initial and final set describe the stiffening of a standardized cement...Read the articleRock Mechanics Testing28 Feb 2026Rock Core Prep Done Right: Why Trimming And End Grinding MatterRock core testing provides the “intact rock” parameters engineers use to inform excavation strategy, stability checks, and deformation expectations in projects like mining, tunneling, and dams. Those lab programs typically report compressive strength (uniaxial or triaxial) and, when stress strain data are captured, stiffness values such as Young’s modulus and Poisson’s ratio. Even with good testing, intact core results are not the same as in situ rock mass behavior, since joints, weakness planes, and heterogeneity strongly influence real structures. That is exactly why preparation matters: standards treat specimen prep as part of the test, requiring cores to be cut to length and their ends machined flat, with dedicated guidance on meeting and...Read the articleCement & Concrete Testing29 Nov 2024Most Popular Types of Material Testing EquipmentTo sum upThe field of material testing includes an extensive number of procedures used to evaluate the properties and performance of materials. These procedures range from assessing mechanical characteristics such as tensile strength, hardness, and impact resistance to evaluating thermal properties like conductivity and expansion. Central to these evaluations are material testing tools, which provide the precise measurements necessary to verify that materials are reliable and safe to use. The selection of testing equipment is comprehensive, reflecting the diversity of materials—including metals, polymers, ceramics, and composites—and the specific tests required for each. For instance, metals may undergo tensile, hardness, and fatigue tests, each...Read the articleRock Mechanics Testing19 Aug 2024Semi-Automatic Core Grinding Machine – A ReviewCreating a specimen is one thing but making sure that it is properly prepared for testing is another. In the field of material testing, the precision with which a specimen is prepared directly impacts the reliability and accuracy of the data obtained. This is why core grinding machines are becoming increasingly vital for laboratories and testing facilities around the world. These machines are designed to guarantee that your specimens meet the highest standards, allowing for precise and valuable insights into the materials being tested. At NextGen, we are leading the way in the industry standards. With years of experience and a strong track record in supplying cutting-edge material testing equipment, we understand what it takes to satisfy our...Read the articleRock Mechanics Testing12 Apr 2024Breaking Down the Process of Ceramic Sample PreparationCeramics stand out for their exceptional properties, including high hardness, thermal stability, and resistance to wear and corrosion. These qualities make ceramics indispensable in many industries, including the electronics, aerospace, automotive, and biomedical industries. The application of ceramics ranges from simple household items like pottery and tiles to complex components such as semiconductor wafers, engine components, and biomedical implants. Ceramics' inherent characteristics, such as their brittleness and diversity of composition, require careful preparation and testing, however. Ceramic sample preparation is a critical step in the material science field. Proper specimen preparation is fundamental as it directly impacts the accuracy and...Read the article